FEEO FPVM-250 2P 550V DC MCCB
FEEO FPVM-250 2P 550V DC MCCB
FEEO Solar 2P DC MCCB, Industrial Breaker, is designed to distribute power and protect the circuit
and power equipment against overload in solar system. It is apply to rating current 1250A or less,
direct current rating voltage 1500V or less. Products according IEC60947-2, GB14048.2 standard.
Model |
FPVM-125 |
FPVM-250 |
FPVM-400 |
FPVM-630 |
FPVM-800 |
FPVM-1250 |
||||||||||||||||||
Rated Continuous Current |
125 |
250 |
400 |
630 |
800 |
1250 |
||||||||||||||||||
Rated Current In (A) |
16、20、25、32、40、50、63、80、100、125 |
100、125、140、160、180、200、225、250 |
250、315、350、400 |
400、500、630 |
630、700、800 |
800、1000、1250 |
||||||||||||||||||
Rated Operating Voltage Ue(V)DC |
500V、550V、750V、1000V |
500V、550V、750V、1000V |
500V、550V、750V、1000V |
500V、550V、750V、1000V |
500V、550V、750V、1000V |
500V、550V、750V、1000V |
||||||||||||||||||
Rated Insulation Voltage Ui (V) |
1000V |
1000V |
1500V |
1500V |
1500V |
1500V |
||||||||||||||||||
Uimp (KV) |
8KV |
8KV |
8KV |
8KV |
8KV |
8KV |
||||||||||||||||||
Test Voltage One Minute(V) |
3550 |
3550 |
3550 |
3550 |
3550 |
3550 |
||||||||||||||||||
Breaking Capacity (KA) Icu(1cs=75%Icu) |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
||||||
250V |
25 |
35 |
50 |
35 |
50 |
65 |
35 |
50 |
65 |
35 |
50 |
65 |
50 |
65 |
80 |
50 |
65 |
80 |
||||||
500V |
25 |
25 |
50 |
35 |
35 |
65 |
35 |
35 |
65 |
35 |
35 |
65 |
50 |
50 |
80 |
50 |
50 |
80 |
||||||
750V |
25 |
15 |
50 |
35 |
25 |
65 |
35 |
25 |
65 |
35 |
25 |
65 |
50 |
35 |
80 |
50 |
35 |
80 |
||||||
1000V |
25 |
10 |
50 |
35 |
15 |
65 |
35 |
15 |
65 |
35 |
15 |
65 |
50 |
20 |
80 |
50 |
20 |
80 |
||||||
Mechanical Life |
Times |
7000 |
7000 |
4000 |
4000 |
2500 |
2000 |
|||||||||||||||||
Electrical Life |
Times |
2000 |
2000 |
1000 |
1000 |
800 |
600 |
|||||||||||||||||
Breaking Times(ms) |
20 |
20 |
20 |
20 |
20 |
20 |
||||||||||||||||||
Installation Location |
Any place |
|||||||||||||||||||||||
Isolator Capacity |
Yes |
|||||||||||||||||||||||
Standard |
IEC 60947-2、IEC60947-1、GB 14048.1、GB 14048.2 |
|||||||||||||||||||||||
Temperature(℃ ) |
-25℃ ~50℃ |
|||||||||||||||||||||||
Protection Degree |
IP20 |
|||||||||||||||||||||||
Accessory |
OF/SD/MX |
|||||||||||||||||||||||
Arcing Distance(mm) |
≥50 |
Shipping & Returns
Shipping & Returns
Available, please review our Refund policy for more details.